Heavy Equipment Repair

How to Solve PCC1302 Code 1472 High AC Current Shutdown

This instruction show you guide on how to solve PCC1302 PowerCommand Code 1472 high AC current shutdown.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Logic:
The generator output current has exceeded at least 150% of rated current.

Possible Causes:
1 Short or overload

2 Incorrect CTs, CT connections, or CT setup
3 CT harness connections
4 Incorrect rating setup

Diagnosis and Repair:
1 Short or overload

a Inspect the load cables and the AC harness connections.
b Disconnect the AC harness from the load cables.
c Inspect the AC harness and board connector pins.
d Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins.
e Check for a short circuit to engine block ground.

2 Incorrect CTs, CT connections, or CT setup
a Check CTs.
a Check that correct CT’s have been installed.
b Check that CT connections are secure by zip ties to corresponding wires.
c Check that CTs are installed in the correct order.
d Connect InPower.
e Verify the correct CT ratio has been entered in the generator setup.
f Adjust the setting(s) as necessary.

3 CT harness connections
a Measure the resistance of the CT harness on each pin.
b Disconnect connector P12 from the control board and CTs.
c Verify the resistance from board connector to CT connections. Resistance should be 5 ohms or less.
d Measure the resistance of each pin on the CT harness connector to engine block ground. Resistance should be open or infinite.
e Verify the CT connections are correct from P12 to the CT terminals.
P12–1 (CT1) to P12–4 (CT1–COM)
P12–2 (CT2) to P12–5 (CT2–COM)
P12–3 (CT3) to P12–6 (CT3–COM)
f Re-terminate connections as necessary.

4 Incorrect rating setup
a Connect InPower.
b Verify the generator rating in the control is set correctly.
c Verify CT ratings in the control are set correctly.
d Adjust settings as necessary

auto

Recent Posts

QSK60 CM2358 Engine Camshaft Speed/Position Sensor Data Erratic Incorrect

This illustration show you guide on how to repair Cummings QSK60 CM2358 engine camshaft speed/position…

6 days ago

Fendt MT800E Tractor DEF Tank Temperature Does Not Change Solution

Here is the instruction show yo guide on how to solve Fendt MT800E tractor DEF…

1 week ago

HITACHI Construction 4JJ1 P0092 Fuel Pressure Regulator Control Circuit High

Here car-auto-repair.com show you guide on how to solve ISUZU construction 4JJ1 engine P0092 fuel…

1 week ago

How to Solve Perkins 1106D EPG Engine E398 Low Fuel Rail Pressure Error

Here is the illustration show you guide on how to solve Perkins 1106D electric power…

1 week ago

Deutz EMR3 Aassembly Inspection and Initialisation Test Guide

Here comes the instruction on how to use SerDia2010 to perform assembly inspection and initialization…

2 weeks ago

HITACHI ZX-5 Excavator No Load Max Differential Pressure Measurement Guide

This instruction show you guide on how to perform No load max differential pressure measurement…

2 weeks ago