How to Solve PCC1302 Code 1472 High AC Current Shutdown

This instruction show you guide on how to solve PCC1302 PowerCommand Code 1472 high AC current shutdown.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Logic:
The generator output current has exceeded at least 150% of rated current.

Possible Causes:
1 Short or overload

2 Incorrect CTs, CT connections, or CT setup
3 CT harness connections
4 Incorrect rating setup

Diagnosis and Repair:
1 Short or overload

a Inspect the load cables and the AC harness connections.
b Disconnect the AC harness from the load cables.
c Inspect the AC harness and board connector pins.
d Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins.
e Check for a short circuit to engine block ground.

2 Incorrect CTs, CT connections, or CT setup
a Check CTs.
a Check that correct CT’s have been installed.
b Check that CT connections are secure by zip ties to corresponding wires.
c Check that CTs are installed in the correct order.
d Connect InPower.
e Verify the correct CT ratio has been entered in the generator setup.
f Adjust the setting(s) as necessary.

3 CT harness connections
a Measure the resistance of the CT harness on each pin.
b Disconnect connector P12 from the control board and CTs.
c Verify the resistance from board connector to CT connections. Resistance should be 5 ohms or less.
d Measure the resistance of each pin on the CT harness connector to engine block ground. Resistance should be open or infinite.
e Verify the CT connections are correct from P12 to the CT terminals.
P12–1 (CT1) to P12–4 (CT1–COM)
P12–2 (CT2) to P12–5 (CT2–COM)
P12–3 (CT3) to P12–6 (CT3–COM)
f Re-terminate connections as necessary.

4 Incorrect rating setup
a Connect InPower.
b Verify the generator rating in the control is set correctly.
c Verify CT ratings in the control are set correctly.
d Adjust settings as necessary

auto

Recent Posts

Kubota L3301 L3901 L4701 Excavator Neutral Adjusting

This instruction show guide on how to adjust neutral for Kubota L330 L3901 L4701 excavator.…

16 hours ago

PCC1302 PowerCommand Code 1992 – Engine Crankshaft Speed Above Rated Speed

PCC1302 PowerCommand Code 1992 - Engine Crankshaft Speed Above Rated Speed Solution. Engine speed signals…

2 days ago

Caterpillar C9 00 246-11 247-11 Brake Pedal Switch Fault Solution

Here is the instruction show you guide on how to solve Caterpillar C9 00 246-11…

3 days ago

How to Solve Allison 3000 & 4000 Gen5 Engine Trouble Code P0703

This instruction show you guide on how to solve Allison 3000 & 4000 Gen5 engine…

6 days ago

How to Solve Fendt MT1149 Tractor SCR System Emptying Not Completed

Here is the illustration show you guide on how to solve Fendt MT1149 tractor SCR…

2 weeks ago

How to Set Play Between Timing Pinion Teeth for CLAAS AXION 920 Tractor?

Here is the instruction show you guide on how to set play between timing pinion…

2 weeks ago