PCC1302 PowerCommand Code 2729 2731 IO Module Lost Error Solution

Here is the instruction show you guide on how to repair PCC1302 PowerCommand Code 2729 2731 IO Module Lost Error.
PCC1302-Power-Engine

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Code 2729 – IO Module Lost (Warning)
Indicates an intermittent data link between the I/O module and the PCC control (Aux 101 I/O
Module option) and no input fault levels were set to Shutdown.

Possible Causes:
1. Incorrect Wiring
2. I/O settings misconfigured

Diagnosis and Repair:
1. Incorrect Wiring
a. Connection between AUX 101 and PCC 1302 is incorrect. Ensure proper wiring.
a. PCC 1302 TB1-1 – PCC Net A (+) to AUX 101 J1-3
b. PCC 1302 TB1-2 – PCC Net B (-) to AUX 101 J1-4
c. PCC 1302 TB1-3 – B+ Return to AUX 101 J14-2
d. PCC 1302 TB1-5 – Customer Fused B+ to AUX 101 J14-1
e. PCC 1302 TB15-5 – System Wake-up to AUX 101 J1-5
2. I/O settings misconfigured
a. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments > System I/O Adjustment > Output Relays ensure System IO Board Enable is disabled.
b. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments > System I/O Adjustment > ensure no inputs or outputs are configured as enabled.

Code 2731 – IO Module Lost (Shutdown)
Indicates an intermittent data link between the I/O module and the PCC control (Aux 101 I/O
Module option) and at least one input fault level was set to Shutdown.

Possible Causes:
1. Incorrect Wiring
2. I/O settings misconfigured

Diagnosis and Repair:
1. Incorrect Wiring
a. Connection between AUX 101 and PCC 1302 is incorrect. Ensure proper wiring.
a. PCC 1302 TB1-1 – PCC Net A (+) to AUX 101 J1-3
b. PCC 1302 TB1-2 – PCC Net B (-) to AUX 101 J1-4
c. PCC 1302 TB1-3 – B+ Return to AUX 101 J14-2

d.PCC 1302 TB1-5 – Customer Fused B+ to AUX 101 J14-1
e. PCC 1302 TB15-5 – System Wake-up to AUX 101 J1-5

2. I/O settings misconfigured
a. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments > System I/O Adjustment > Output Relays ensure System IO Board Enable is disabled.
b. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments >System I/O Adjustment > ensure no inputs or outputs are configured as enabled.

 

Refer to the engine manual for correct threshold values and make the appropriate changes using InPower v14.5 pro.