PCC1302 PowerCommand Code 488 Intake Manifold Temperature High Solution

This instruction show you guide on how to repair PCC1302 PowerCommand trouble code 488 intake manifold temperature High (Warning).Engine intake manifold temperature has exceeded 185° F (85° C) for more than 90 seconds.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

Possible Causes:
1 High ambient temperature
2 Radiator blocked
3 Louvers are closed or damaged
4 Charge air cooler fins or radiator fins are damaged or obstructed
5 Fan belt is broken or loose
6 Fan drive or fan controls are malfunctioning
7 Inaccurate coolant temperature sensor
8 Fault simulation feature is enabled
9 Incorrect threshold setting

Diagnosis and Repair:
1 High ambient temperature
a Use a thermocouple to verify air temperature entering intake louver of generator.
b Reduce loads or recirculation of discharge air to generator in elevated ambient.

2 Radiator blocked
a Inspect radiator for debris or blockages.
b Remove blockage or winterfront as applicable.

3 Louvers are closed or damaged
a Inspect louvers for proper operation.
b Repair or replace if damaged.
c Check louver motor for proper operation.
d If louver motor is operational, verify louver shutter thermostat is operational.

4 Charge air cooler fins or radiator fins are damaged or obstructed
a Inspect for dirt, debris or obstructions.
b Clean if necessary.

5 Fan belt is broken or loose
a Inspect belt(s) for damage, wear, and proper tension.
b Repair or replace if damaged or worn.
6 Fan drive or fan controls are malfunctioning
a Inspect pullies and belt tensioner for damage or wear.
b Repair or replace if damaged or worn.

 

7 Inaccurate coolant temperature sensor
a Use a thermocouple or similar device to measure coolant temperature near sender and compare to coolant temperature displayed.
b Verify the temperature sender resistance and compare to specifications called out in the engine manual.
c Verify continuity from temperature sender wire to engine ECM. Harness resistance should be less than 5 Ohms.
d Repair or replace faulty components or wiring.

8 Fault simulation feature is enabled
a Use the service tool to connect to the engine ECM and verify fault override toggle is disabled.
b Reconfigure generator and disable fault overrides.

9 Incorrect threshold setting
a Use the service tool to connect to the engine ECM and verify fault threshold settings and compare to the specifications called out in the engine manual.
b Verify ECM and PCC calibration number and revision is correct.
c Recalibrate the engine ECM to reset the threshold settings.

 

More repair cases please refer to:PCC1302 PowerCommand trouble repair

auto

Recent Posts

PACCAR Brake Saver Oil Temperature Gauge Inoperative DTC138703 and DTC138704

This instruction show you guide on how to solve PACCAR brake saver oil temperature gauge…

3 hours ago

Deutz EMR3 Engine Trouble Code 19 / 676 / ArHtCD_NoLd Solution

This instruction show you guide on how to solve Deutz EMR3 engine trouble code 19…

21 hours ago

Fendt 1000 S4 Tractor 1001 Crossgate Lever Calibration Guide

Here is the instruction show you guide on how to calibrate 1001 crossgate for Fendt…

3 days ago

How to Adjust Neutral for Kubota L3901 Tractor Transmission

This instruction show you guide on how to adjust neutral Kubota L3901 tractor transmission.  …

5 days ago

ISUZU Construction 4JJ1 Engine P0089 Fuel Rail Pressure Regulator Performance

Here is the instruction show you guide on how to solve ISUZU construction 4JJ1 engine…

1 week ago

Massey Ferguson Tractor 6700 Trouble Code SPN 97, FMI 31 Water in Fuel

Here is the instruction show you guide on how to solve Massey Ferguson tractor 6700…

1 week ago