PCC1302 PowerCommand Low Coolant Level (Warning or Shutdown) Solution
Related Contents:
2024 InPower V14.5 Pro V12 Diagnostic Software Free Download
PowerCommand Diagnostic 9 Pin Adapter Cable for InPower
Logic:
This fault is used when an optional coolant level sensor is installed. The nature of the fault is an optional customer selection.
The fault function can be programmed (using the InPower service tool), as follows:
• Enable/disable input (Default: enable)
• Status, Warning, or Shutdown (Default: #1-None, #2 and #3-Warning)
• Active closed or open (Default: closed [ground])
• Change the display name using up to 19 characters (Default: #1- Customer Fault 1, #2-Ground Fault, #3-Low Fuel)
Possible Cause:
1 Low coolant
2 No actual fault, external wiring problem
Diagnosis and Repair:
1 Low coolant
a If the generator set is powering critical loads and cannot be shut down, wait until next shutdown period, then do the steps that follow.
b Allow engine to completely.
c Check coolant level and replenish if low.
2 No actual fault, external wiring problem
a Disconnect the signal lead from TB1 and reset the control.
a CONFIG INPUT 1 – TB1-13
b If the message goes away, the external wiring has a short circuit. Grounding of either input activates fault.
This instruction show you guide on how to remove second tank for CLAAS AXION 960-920…
This instruction show you guide on how to solve Doosan excavator P0408 maximum EGR rate…
Here is the instruction show you guide on how to calibrate 2403 steering valve for…
This function requires all connectors to be disconnected from all electrohydraulic valves on the tractor.You…
This instruction show you guide on how to remove center joint and center frame for…
How to solve Doosan heavy duty machine P0100 fault code signal error of air mass…